Voltage Drop Calculator
Work out the voltage drop on a circuit you already have in mind — volts and percentage together, checked against the 3% and 5% figures, with the maximum run length that conductor has left at your load.
Last checked against the code
Voltage Drop Calculator
NEC (US)How this was derived
- Formulaone-way distance
- —
- Conductor areacircular mils
- —
- Volts at the load
- ——
How this is calculated
A conductor is a resistor. Push current through it and some of the supply voltage is spent getting to the far end rather than arriving there. How much depends on three things: how much current is flowing, how far it has to travel, and how much metal there is to travel through.
The industry-standard form of the calculation works in circular mils, a unit invented for exactly this purpose — the area of a circle one thousandth of an inch across, defined so that area in circular mils is simply the diameter in mils squared, with no π anywhere:
Vdrop = (2 × K × I × D) ÷ CM for single phase, andVdrop = (1.732 × K × I × D) ÷ CM for a balanced three-phase load. The percentage is then that figure divided by the system voltage and multiplied by a hundred.
D is the one-way distance. Panel to load, measured along the route the cable takes. The factor of 2 in the single-phase version is the return conductor — current goes out on one leg and comes back on the other, so the loss happens over twice the one-way length. This is worth being pedantic about because calculators differ: some ask for total conductor length instead, and the two conventions produce answers exactly a factor of two apart. Three phase uses 1.732 rather than 2 for a different reason entirely. A balanced three-phase load has essentially no neutral current, so there is no return leg to account for; the √3 is the relationship between line and phase quantities.
K is a resistivity constant, about 12.9 for copper and 21.2 for aluminium, in ohm-circular-mils per foot. It is a convention rather than a measurement: it folds a reference temperature of roughly 75 °C and an allowance for stranding into one number, and published values run from 12.0 to 12.9 for copper depending on which assumptions a given reference makes. The higher figure used here is the conservative one — it predicts slightly more drop than a lightly-loaded conductor in a cool space will actually show.
What this leaves out, honestly. AC impedance is not just resistance. A conductor carrying alternating current also has inductive reactance, and the true drop is the vector sum of a resistive and a reactive component at the load's power factor. The formula above ignores reactance entirely. That is the standard simplification, and it is a good one: reactance is roughly constant per foot regardless of conductor size while resistance falls as the conductor gets fatter, so on the small conductors and modest runs that make up almost all branch-circuit work the reactive term disappears into the rounding. It stops being negligible on large conductors — roughly 4/0 and up — and in steel raceway, where the magnetic path amplifies it. There, NEC Chapter 9 Table 9 publishes real effective-impedance values per raceway type and power factor, and it is the right reference. This calculator says so when your inputs land in that territory rather than quietly being a percent or two optimistic.
Worked example
One full calculation with real numbers, so you can follow along and check the tool by hand.
A 10 AWG copper conductor feeding a 50 A load, 100 ft from a 240 V single-phase panel. Every number below comes from the same module the calculator above runs.
Step one, the conductor area. 10 AWG is10,380 circular mils. That figure is geometry, not code — AWG is a fixed geometric progression, so it does not change between editions.
Step two, the volts. Single phase, so the multiplier is 2: (2 × 12.9 × 50 × 100) ÷ 10,380 = 129,000 ÷ 10,380 =12.43 V.
Step three, the percentage. 12.43 ÷ 240 × 100 =5.18%. The load sees227.57 V rather than 240 V.
Step four, the comparison. 5.18% is past the 3% branch-circuit figure and past the 5% combined figure as well. Neither is enforceable code text in most installations, so this is not automatically a violation — but it is well outside normal design practice, and the run would have to stop at about 58 ft to hold 3% at this load. To make 100 ft work you would need17,917 cmil, which means stepping up to 6 AWG.
And a fifth step the arithmetic does not tell you. 50 A on 10 AWG is not a legal circuit in the first place. Table 310.16 gives 10 AWG copper 35 A in the 75 °C column and 40 A even at 90 °C, and 240.4(D) caps its overcurrent device at 30 A regardless. The drop figure above is perfectly correct and completely beside the point: this is a diagnostic tool, and it will tell you the drop on any combination you hand it, including one that should never be installed. That is why it warns rather than refuses, and why the ampacity question belongs to a different page.
Visual comparison
- Branch-circuit target: 3 %
| One-way distance (ft) | Voltage drop% | Against the guidance |
|---|---|---|
| 0 | 0 | within 3% |
| 25 | 0.78 | within 3% |
| 50 | 1.55 | within 3% |
| 75 | 2.33 | within 3% |
| 100 | 3.11 | 3–5% |
| 125 | 3.88 | 3–5% |
| 150 | 4.66 | 3–5% |
| 175 | 5.44 | over 5% |
| 200 | 6.21 | over 5% |
| 225 | 6.99 | over 5% |
| 250 | 7.77 | over 5% |
| 275 | 8.54 | over 5% |
| 300 | 9.32 | over 5% |
Source: Circular-mil method at K = 12.9; areas from the AWG geometric series
At 30 A, 10 AWG copper on a 240 V single-phase circuit crosses 3% at about 97 ft. Everything to the left of that crossing is inside the recommended figure.
Reference tables
This is the table to reach for when the question is "how far can I run this", which is most of the time. Every row is the longest one-way run that stays inside 3% for that conductor, in copper, at the load in the second column.
About that load column. It is the 60 °C ampacity from Table 310.16, which is what NM cable and most residential terminations are held to — so 14 AWG pairs with 15 A, 12 AWG with 20 A, 10 AWG with 30 A and 8 AWG with 40 A. Those are the pairings people mean when they ask about twelve-gauge on a 20 amp circuit. If your actual load is lighter, the distance stretches in exact proportion: half the current goes twice as far, and the numbers below are the pessimistic end of the range rather than a wall.
Two patterns are worth taking away. The 240 V column is close to double the 120 V column throughout, and the 208 V three-phase column lands almost exactly on the 240 V single-phase one — which is why moving a long run to a higher voltage is so often cheaper than moving it to a bigger conductor.
The second is subtler and more useful: distance grows far more slowly than the conductor does. Going from 14 AWG to 4/0 multiplies the cross-section by fifty and the run length by only four, from 76 ft to 303 ft, because each step up the ladder is paired with a load that has grown almost as fast — 15 A becomes 195 A. Upsizing a conductor while the load stays put does buy distance in direct proportion to area; upsizing because the load grew buys you almost nothing. That is the trap behind "just run a bigger wire" on a circuit whose load is growing at the same time.
For aluminium, multiply every distance by roughly 0.61 — the ratio of the two K values — or just run the calculator, which does it exactly.
| Wire size | LoadA (60 °C) | 120 V singleft | 240 V singleft | 208 V threeft |
|---|---|---|---|---|
| 14 AWG | 15 | 38 | 76 | 77 |
| 12 AWG | 20 | 46 | 91 | 91 |
| 10 AWG | 30 | 48 | 97 | 97 |
| 8 AWG | 40 | 58 | 115 | 115 |
| 6 AWG | 55 | 67 | 133 | 133 |
| 4 AWG | 70 | 83 | 166 | 167 |
| 3 AWG | 85 | 86 | 173 | 173 |
| 2 AWG | 95 | 97 | 195 | 195 |
| 1 AWG | 110 | 106 | 212 | 212 |
| 1/0 AWG | 125 | 118 | 236 | 236 |
| 2/0 AWG | 145 | 128 | 256 | 256 |
| 3/0 AWG | 165 | 142 | 284 | 284 |
| 4/0 AWG | 195 | 151 | 303 | 303 |
| 250 kcmil | 215 | 162 | 324 | 325 |
| 300 kcmil | 240 | 174 | 349 | 349 |
| 350 kcmil | 260 | 188 | 376 | 376 |
| 400 kcmil | 280 | 199 | 399 | 399 |
| 500 kcmil | 320 | 218 | 436 | 436 |
| 600 kcmil | 350 | 239 | 478 | 479 |
| 700 kcmil | 385 | 254 | 507 | 508 |
| 750 kcmil | 400 | 262 | 523 | 524 |
Notes and exceptions
This page checks a conductor; it does not choose one. The distinction matters because the two jobs need different inputs and produce different answers. Voltage drop is one of two independent constraints on a conductor, and it is not always the binding one — a short run with a heavy load is decided by ampacity, and no amount of drop calculation will reveal that. If you are starting from a load and a run length with no size in mind, thewire size calculator runs both checks and tells you which one governed. If you have a size and want to know what it does, you are in the right place.
What is deliberately not modelled here. Power factor is taken as unity, which is right for resistive loads and optimistic for motors and switching supplies. The conductor is assumed to be at roughly 75 °C, baked into K; a cool conductor drops meaningfully less. Reactance is ignored, as described above. Paralleled conductors under 310.10(G) are not handled — the effective area is the sum of the set, so a calculation is possible by hand, but the derating that comes with paralleling is not. And a shared neutral carrying unbalanced current on a multiwire branch circuit adds drop this single-circuit model does not see.
Starting voltage matters as much as the conductor. The percentage here is measured against whatever you enter as the system voltage. If you are diagnosing a real complaint rather than designing a new circuit, measure the supply at the panel under load and enter that. A circuit that calculates at 2.8% against a nominal 240 V is a different conversation if the panel is actually sitting at 231 V, because the load is then already down before your conductor has taken its share.
Common mistakes
Entering the round-trip length instead of the one-way distance
This page takes the one-way distance and doubles it internally — the × 2 in the formula is the return conductor. Some references define the input as total conductor length instead. Get the convention backwards and the answer is exactly twice or half what it should be.
Calculating against nominal voltage rather than measured voltage
A 240 V service rarely sits at 240 V. If the supply is really 232 V, a 7 V drop is 3.0% rather than 2.9%, and the load sees 225 V. When you are troubleshooting rather than designing, measure the source and use that figure.
Using the breaker rating as the load current
Drop is proportional to the current actually flowing, not to the protection. A 20 A circuit carrying 7 A drops about a third of what the 20 A figure suggests. Design at the expected load; troubleshoot at the measured one.
Measuring the run on the drawing instead of along the route
Conductor length includes the drop down the wall, the climb over the ductwork, the detour around the beam and the tail coiled in the panel. A straight-line measurement on a floor plan routinely comes up 20% short.
Treating 3% as a hard code limit
Both 3% and 5% come from informational notes, which are explanatory rather than enforceable. Some circuit types and some jurisdictions do mandate a figure. Calling a 3.4% branch circuit a violation is as wrong as ignoring the number entirely.
NEC 2023 210.19(A) Informational Note 4
This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.
Frequently asked questions
How do you calculate voltage drop?
For a single-phase circuit, multiply 2 × K × the current in amps × the one-way distance in feet, then divide by the conductor’s area in circular mils. K is a resistivity constant, about 12.9 for copper and 21.2 for aluminium. For a balanced three-phase circuit, use 1.732 in place of the 2. Divide the result by the system voltage and multiply by 100 to get the percentage.
What is an acceptable voltage drop?
3% on a branch circuit and 5% for the feeder and branch circuit combined are the figures almost everyone works to. They come from informational notes in the NEC rather than from enforceable code text, so in most installations they are a design recommendation rather than a pass/fail test. Specific articles do mandate limits — photovoltaic circuits under 690.8 and sensitive electronic equipment under 647.4(D) among them — and some jurisdictions adopt the 3% figure by local amendment.
How far can I run 12 gauge wire on a 20 amp circuit?
About 46 feet at 120 V and about 91 feet at 240 V, if you want to stay inside 3% at the full 20 A. The doubling is because a 240 V circuit both draws half the current for the same power and has twice as many volts for the 3% to be measured against. At a lighter actual load the distance stretches proportionally — the same conductor carrying 10 A goes twice as far.
Is voltage drop worse at 120 V than at 240 V?
Yes, by a factor of four for the same power delivered. Halving the voltage doubles the current, which doubles the volts lost, and those volts are then measured against a supply half the size. It is why long runs to outbuildings are almost always worth doing at 240 V, and why the same conductor that struggles on a 120 V circuit is comfortable on a 240 V one.
Does voltage drop actually matter if nothing trips?
Nothing will trip — that is precisely the problem, because the fault passes inspection and then persists. Motors draw more current at reduced voltage and run hotter for it, which shortens winding life. Resistive heaters deliver power in proportion to the square of the voltage, so a 5% drop costs nearly 10% of the heat. LED drivers and electronic controls can flicker or drop out near the bottom of their input window. The lost volts leave as heat in the conductor and are billed for.
Why does this calculator ignore reactance?
It uses the DC-resistance approximation, which is the industry-standard simplification and is accurate to well within a tenth of a percentage point on the conductor sizes and run lengths that make up nearly all branch-circuit work. Reactance matters at larger sizes — roughly 4/0 and up — and in steel raceway, where NEC Chapter 9 Table 9 publishes real effective impedance values per raceway type. This page flags results where that becomes relevant rather than pretending the simplification is universal.