Motor FLA Calculator

Look up the NEC full-load current for a single-phase or three-phase motor, and get the conductor and breaker sizes Article 430 derives from it — the table value the code requires, not the figure on the nameplate.

Last checked against the code

Motor FLA Calculator

NEC (US)
Caution: Use these figures, not the motor's nameplate. For sizing conductors, the disconnect and the branch-circuit short-circuit and ground-fault protection, the code requires the value from Table 430.248 or 430.250 — even when the nameplate on the motor in front of you says something different, and even when the nameplate figure is lower. The nameplate current is used to set the overload device under 430.32, and for nothing else on this circuit.NEC 2023 430.6(A)(1)
Phase
Single-phase reads Table 430.248 and stops at 10 HP. Three-phase reads Table 430.250 and starts at 1/2 HP.

How this is calculated

Caution: This is a lookup, and that is a code requirement rather than a convenience. There is a formula for motor current, and the NEC does not let you use it here. Conductors, the disconnect and the branch-circuit protection are all sized from Table 430.248 or Table 430.250 — not from a calculation, and not from the current printed on the motor.NEC 2023 430.6(A)(1)

A motor circuit is protected by two devices doing different jobs, and almost everything confusing about Article 430 follows from that split.

The overload device — typically the heaters or electronic overload block in the starter — protects the motor and its conductors from running too hot over minutes and hours. It is sized under 430.32 from thenameplate current, because that is a property of the actual machine installed.

The branch-circuit short-circuit and ground-fault device — the breaker or fuse in the panel — clears faults in milliseconds and otherwise stays out of the way. It has to be big enough to ride through a starting inrush of six to eight times running current without tripping. It is sized under 430.52 from thetable value.

That is the whole reason for 430.6(A)(1). The nameplate belongs to one motor; the circuit outlives it. Standardising the sizing basis means a compliant replacement motor of the same rating still works on the same conductors in ten years.

From the table figure, two calculations run in opposite directions.

430.22, the conductor: 125%, rounded up. Branch-circuit conductors must have an ampacity of at least 125% of the table full-load current. That is a minimum, so you take the next conductor that meets it.

430.52, the device: a table percentage, rounded down. How far above full load the device may be rated depends on what kind of device it is — Table 430.52 gives a different figure for each, and 250% is the column for the inverse-time circuit breaker this page assumes. That figure is a permittedmaximum, which is what sends the rounding the other way. The FAQ below sets the two directions side by side.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

A 5 HP three-phase motor on a 230 V system. Squirrel-cage induction, started across the line, protected by an ordinary inverse-time circuit breaker.

Step one, the lookup. Table 430.250, the 5 HP row, the 230 V column: 15.2 A. Nothing is calculated here and nothing is read off the motor. If the nameplate on this particular machine says 14.2 A, or 16.0 A, it makes no difference to any of what follows — that number is for the overload relay.

Step two, the conductor. 430.22 wants at least 125% of that:15.2 × 1.25 = 19 A. Reading up Table 310.16 at the 75 °C copper column, the smallest conductor carrying 19 A is 14 AWG, rated 20 A. At the 60 °C column the answer would be 12 AWG, which is what to use where the terminations at either end are not rated higher.

Step three, the breaker. Table 430.52 permits an inverse-time breaker at up to 250% of full-load current: 15.2 × 2.5 =38 A. That is a ceiling, so rounddown to the largest standard rating underneath it — which is35 A, with 3 A of headroom unused.

40 A is a standard rating too, and sits only 2 A above the ceiling — which is precisely why this step is worth doing deliberately rather than by eye.

So the circuit is 14 AWG conductors behind a 35 A breaker, with the overload device set separately once the nameplate is in front of you. Every figure above came from one row of one table.

Visual comparison

Full-load current by horsepower — three-phase at 230 VAlmost, but not quite, a straight line. The amps-per-horsepower column is what to watch: a 1 HP motor costs 4.2 A per horsepower where a 50 HP motor costs 2.6, because efficiency and power factor both improve with size. That is why doubling the motor never quite doubles the circuit, and why estimating a big motor by scaling up a small one overshoots.
Full-load current by horsepower — three-phase at 230 V
MotorBarFull-load current (A)Per HP
1 HP4.24.2 A per HP
1-1/2 HP64 A per HP
2 HP6.83.4 A per HP
3 HP9.63.2 A per HP
5 HP15.23 A per HP
7-1/2 HP222.9 A per HP
10 HP282.8 A per HP
15 HP422.8 A per HP
20 HP542.7 A per HP
25 HP682.7 A per HP
30 HP802.7 A per HP
40 HP1042.6 A per HP
50 HP1302.6 A per HP

Source: NEC 2023 Table 430.250

The same motors at 230 V and at 460 VTwo lines that are exactly 2:1 apart at every single point, because current is inversely proportional to voltage at constant power. This is the whole argument for 480 V distribution in a plant: the same 50 HP motor needs 130 A at 230 V and 65 A at 460 V, which is the difference between 1/0 and 4 AWG feeders over what may be a long run.
  • 230 V
  • 460 V
The same motors at 230 V and at 460 V — data
Motor230 VA460 VA
1 HP4.22.1
1-1/2 HP63
2 HP6.83.4
3 HP9.64.8
5 HP15.27.6
7-1/2 HP2211
10 HP2814
15 HP4221
20 HP5427
25 HP6834
30 HP8040
40 HP10452
50 HP13065

Source: NEC 2023 Table 430.250

Reference tables

Both tables in full, because they are the point of the page — a lookup tool whose table is hidden behind a form is less useful than the table. Use these when you are checking someone else's figure, pricing a job from a schedule of motors, or working without a signal on site.

Read across a row and the inverse-voltage relationship is visible: the 115 V and 230 V columns are exactly 2:1, as are 230 V and 460 V on the three-phase table. Read down a column and note where each table stops. Single-phase ends at 10 HP, which is genuinely the practical limit for single-phase motors rather than an omission. Three-phase starts at 1/2 HP and runs to 200 HP.

Table 430.250 — three-phase alternating-current motors
Motor200 VA208 VA230 VA460 VA575 VA
1/2 HP2.52.42.21.10.9
3/4 HP3.73.53.21.61.3
1 HP4.84.64.22.11.7
1-1/2 HP6.96.6632.4
2 HP7.87.56.83.42.7
3 HP1110.69.64.83.9
5 HP17.516.715.27.66.1
7-1/2 HP25.324.222119
10 HP32.230.8281411
15 HP48.346.2422117
20 HP62.159.4542722
25 HP78.274.8683427
30 HP9288804032
40 HP1201141045241
50 HP1501431306552
60 HP1771691547762
75 HP2212111929677
100 HP28527324812499
125 HP359343312156125
150 HP414396360180144
200 HP552528480240192
Source: NEC 2023 Table 430.250, induction-type squirrel cage and wound rotor. The published table also carries 115 V and 2300 V columns, omitted here.
Table 430.248 — single-phase alternating-current motors
Motor115 VA200 VA208 VA230 VA
1/6 HP4.42.52.42.2
1/4 HP5.83.33.22.9
1/3 HP7.24.143.6
1/2 HP9.85.65.44.9
3/4 HP13.87.97.66.9
1 HP169.28.88
1-1/2 HP2011.51110
2 HP2413.813.212
3 HP3419.618.717
5 HP5632.230.828
7-1/2 HP80464440
10 HP10057.55550
Source: NEC 2023 Table 430.248.

Notes and exceptions

One motor, one branch circuit. Everything above sizes a single motor. A feeder supplying several is 430.24: 125% of the largest motor's full-load current plus 100% of every other motor on the feeder, which is neither of the obvious guesses. The feeder's overcurrent device is 430.62, and it is a different calculation again.

The 250% figure is one column of four. Table 430.52 sets a different maximum for every protective device type: 300% for a non-time-delay fuse, 175% for a dual-element time-delay fuse, 250% for the inverse-time breaker this page assumes, and 800% for an instantaneous-trip breaker in a listed combination controller. Selecting the device type is the obvious next revision of this calculator; until it exists, check the column for what you are actually installing. Where a motor will not start on the calculated rating, 430.52(C)(2) permits going higher still, to defined limits.

Some motors are not in these tables at all. Direct-current motors use Table 430.247 and single-phase alternating-current motors of unusual construction may need the manufacturer's data. A hermetic refrigerant motor-compressor — every air conditioner and refrigeration unit — is sized from its rated-load current under 440.6, not from Article 430 tables. Torque motors and synchronous motors running at leading power factor each have their own treatment.

Service factor and design letter change the overload, not the FLA.A motor marked with a service factor of 1.15 or greater gets its overload device set at up to 125% of nameplate under 430.32(A)(1), against 115% for others. None of that touches the table lookup here — but the design letter does matter for the conductor, since motors marked design B, C or D are specifically permitted the 75 °C ampacity that 110.14(C) would otherwise withhold on a circuit of 100 A or less.

Common mistakes

  1. Sizing the circuit from the motor’s nameplate current

    The single most common finding on a motor installation. 430.6(A)(1) requires the table value for conductors, the disconnect and the branch-circuit protection — even when the nameplate reads lower, and even when the motor genuinely draws less. The nameplate figure sets the overload device under 430.32 and nothing else.

    NEC 2023 430.6(A)(1)

  2. Applying the branch-circuit rule to a feeder

    A feeder supplying several motors is not 125% of everything. 430.24 takes 125% of the largest motor’s full-load current plus 100% of every other motor on the feeder. Applying 125% across the board oversizes the feeder; applying 100% across the board undersizes it.

    NEC 2023 430.24

  3. Treating Exception No. 1 as general permission to round up

    The percentage in Table 430.52 rarely lands on a stocked rating, and 430.52(C)(1) Exception No. 1 does allow the next size up — which makes the wrong instinct feel sanctioned. It is a permission for a defined circumstance, not a licence: reach for it deliberately, having first worked out what the ceiling actually was.

    NEC 2023 430.52(C)(1) Ex. 1

  4. Reading the system voltage row instead of the motor voltage row

    A 460 V motor runs on a 480 V system and a 230 V motor on a 240 V one. The tables are indexed by the motor rating, so reaching for a 480 V column that does not exist — or rounding to one that does — puts you one row out and understates the current by about 4%.

    NEC 2023 Table 430.250

  5. Using these tables for equipment that has its own rating

    A hermetic refrigerant motor-compressor uses its rated-load current per 440.6, not Table 430.250. A motor on a variable-frequency drive is sized from the drive’s input rating. Both are common enough that reaching for Article 430 tables by reflex is a real risk.

    NEC 2023 440.6, 430.122

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

Why does the NEC use table values instead of the motor nameplate?

To make the circuit independent of which motor is bolted down at the end of it. Two 5 HP motors from different manufacturers carry different nameplate currents, and the one that replaces them in ten years will differ again — but the conductors are already in the wall by then. Fixing the sizing basis to a published table keeps the installation correct across any compliant motor of that rating.

Why is a motor breaker rounded down when other breakers round up?

Because one rule states a floor and the other states a ceiling. A continuous load fixes how small the device may be, so you go up to reach it. Article 430 fixes how large the device may be, so you come down to stay under it. Rounding the wrong way is a compliance failure in each direction. One caveat: 430.52(C)(1) Exception No. 1 permits the next size up where the calculated figure is not itself a standard rating — a permission to use deliberately, not a default to fall into.

Can a 35 A breaker protect a 14 AWG conductor?

Yes, and it is entirely routine. The 240.4(D) small-conductor rule that would otherwise cap 14 AWG at 15 A simply does not reach a motor circuit — 240.4(G) hands those to Article 430, which protects the conductor with the overload relays in the starter instead of with the device in the panel.

What are the common three-phase motor currents at 460 V?

From Table 430.250: 1 HP is 2.1 A, 3 HP is 4.8 A, 5 HP is 7.6 A, 10 HP is 14 A, 25 HP is 34 A, 50 HP is 65 A and 100 HP is 124 A. A rough field check is a bit over 1.2 A per horsepower at 460 V, drifting down toward 1.24 at the large end as efficiency improves. Double any of them for the 230 V figure.

Do these tables apply to a motor on a variable-frequency drive?

No. 430.122 sizes the conductors feeding a drive from the drive’s rated input current, which often differs substantially from anything in these tables. The wiring between the drive and the motor is a third question again, governed by the manufacturer’s instructions rather than by Article 430.

What is the difference between Table 430.248 and Table 430.250?

Phase, and range. 430.248 covers single-phase motors from 1/6 HP to 10 HP at 115, 200, 208 and 230 V. 430.250 covers three-phase induction motors — squirrel cage and wound rotor — from 1/2 HP to 200 HP, and adds the 460 V and 575 V columns that industrial work runs on. There is no overlap in what they are for: a motor is one or the other, and reading the wrong table gives a number that is wrong by roughly the square root of three.