Breaker Size Calculator

Find the correct standard circuit breaker for a load, with the 125% continuous-load factor applied and the result rounded up to a real NEC device rating — for electricians and estimators sizing general-purpose branch circuits and feeders.

Last checked against the code

Breaker Size Calculator

NEC (US)
What do you know?
Phase
Single phase divides by V; three phase divides by V × 1.732.

Derived load current:

Load type
Continuous means the load runs at its maximum for three hours or more — lighting circuits, HVAC, EV chargers. Those get the 125% factor. A receptacle circuit or a cooktop normally does not.
Note: Motor circuits are out of scope. Motor branch-circuit protection is sized from the Article 430 full-load current tables, at up to 250% for an inverse-time breaker, and this 125% rule would undersize the device and trip on inrush.NEC 2023 Article 430

How this is calculated

A circuit breaker has one job: to open before the conductor it protects overheats. Sizing it is therefore a question of finding the smallest device that will carry the intended load indefinitely without tripping, while still being small enough to protect the wire. The NEC gets there in two steps.

The first step is the 125% continuous-load factor. Section 210.20(A) requires a branch-circuit device to be rated at not less than 125% of the continuous load plus 100% of the non-continuous load, and 215.3 says the same for feeders. The reason is thermal: a breaker is calibrated in open air on a test bench, but installed in a crowded panel it runs warmer and its trip characteristic shifts. The extra 25% is margin against that, not against the load itself. A load is continuous when its maximum current is expected to continue for three hours or more — a definition about duration, not frequency.

The second step is rounding up to a standard rating. Section 240.6(A) lists the ratings that manufacturers actually build: 15, 20, 25, 30, 35, 40, 45, 50, 60, and onwards in widening jumps. A calculation almost never lands on one of them, so the result goes up to the next listed size. Rounding down is not an option, because the device would then be rated below the load it serves.

Read the two steps together and a useful shortcut falls out: since a continuous load is multiplied by 1.25, any device can serve a continuous load of 80% of its rating. A 20 A breaker takes 16 A continuous, a 30 A breaker takes 24 A, and a 100 A breaker takes 80 A. That 80% figure is where the familiar rule of thumb comes from, and it is simply the 125% requirement stated the other way round.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

Two circuits with similar-looking loads land on very different devices, which is the clearest way to see what the load-type question is actually doing.

Case 1 — a 24 A continuous lighting load. A retail floor lit by a run of fixtures drawing 24 A, on from opening to close. That is well past three hours, so the load is continuous and the factor applies: 24 × 1.25 =30 A of required capacity. Looking down the 240.6(A) list, 30 A is itself a standard rating, so the answer is a 30 A breaker with no rounding at all. Worth noticing that this leaves zero headroom — the required capacity sits exactly on the device rating — so if a single extra fixture is added later, the circuit no longer complies.

Case 2 — a 38 A non-continuous load. A commercial cooktop drawing 38 A, used in bursts through a service rather than at full output for three hours. No factor applies, so the required capacity is the load itself: 38 A. That is not a standard rating, so it rounds up to the next one on the list, a40 A breaker, leaving 2 A of headroom.

Now compare them. The second load is more than 50% larger than the first, yet the device only goes up one step, from 30 A to 40 A. And if that same 38 A load were continuous, the arithmetic would be 38 × 1.25 = 47.5 A, which rounds up to a50 A breaker — two steps larger, from the same nameplate current. The load type is doing as much work here as the load itself, and it is the input most often got wrong.

Visual comparison

Standard breaker ratings, 15 A to 600 AThe 240.6(A) ladder. Steps are 5 A apart at the bottom and 100 A apart at the top, so the penalty for exceeding a rating grows sharply with size: a load 1 A over 100 A goes to 110 A, but a load 1 A over 500 A goes to 600 A. Worth checking before accepting a design that sits just above a step.
Standard breaker ratings, 15 A to 600 A — data
RatingAmpsA
15 A15
20 A20
25 A25
30 A30
35 A35
40 A40
45 A45
50 A50
60 A60
70 A70
80 A80
90 A90
100 A100
110 A110
125 A125
150 A150
175 A175
200 A200
225 A225
250 A250
300 A300
350 A350
400 A400
450 A450
500 A500
600 A600

Source: NEC 2023 240.6(A)

Reference tables

The table lists every standard rating this calculator works in, alongside the largest load each device may actually serve. The two load columns are the 125% rule applied in reverse: the non-continuous column is simply the rating, and the continuous column is 80% of it. Read across from a device you already have in the panel to see what it can legitimately carry.

Use the table when you are working backwards — checking whether an existing breaker suits a load you are about to add, or picking a device from stock. Use the calculator when you are working forwards from a known load, particularly in watts mode, where the conversion and the factor compound.

Two limits on the table. It stops at 600 A because beyond that a single branch device stops being the right question and the job becomes a service or feeder study under Article 220. And none of it applies to motors: Article 430 sizes motor protection from its own full-load current tables at up to 250%, and this tool will undersize a motor circuit if you use it there.

Standard breaker ratings and the load each can serve
Device ratingAMax non-continuous loadAMax continuous loadA (80%)
151512
202016
252520
303024
353528
404032
454536
505040
606048
707056
808064
909072
10010080
11011088
125125100
150150120
175175140
200200160
225225180
250250200
300300240
350350280
400400320
450450360
500500400
600600480
Source: NEC 2023 240.6(A) for the ratings; 210.20(A) for the 125% continuous basis.

Common mistakes

  1. Not recognising a load as continuous

    Three hours at full output is a low bar. Office and retail lighting, HVAC compressors, EV chargers, pool pumps and most commercial refrigeration all clear it comfortably. Miss it and the device is undersized by a fifth.

    NEC 2023 Article 100, 210.20(A)

  2. Rounding the load down to a standard size

    The rounding always goes up. A 38 A load takes a 40 A device, never 35 A, because the device must be rated not less than the load it serves. Rounding down is how a circuit ends up nuisance-tripping under normal use.

    NEC 2023 240.4

  3. Sizing the breaker but not the conductor

    The same 125% basis applies to the wire. A 24 A continuous load needs both a 30 A device and a conductor good for 30 A after derating — and derating can easily push that to a larger size than the breaker suggests.

    NEC 2023 210.19(A)

  4. Running this calculation on a motor circuit

    Motor protection comes from Article 430, using the full-load current tables rather than the nameplate amps, and permits an inverse-time breaker at up to 250% of FLC. Applying the 125% rule here trips the motor on starting inrush.

    NEC 2023 430.52

  5. Mixing continuous and non-continuous loads on one circuit

    Where a circuit carries both, the device is sized at 125% of the continuous portion plus 100% of the rest — not 125% of everything. This tool assumes one load type; split the arithmetic manually for a mixed circuit.

    NEC 2023 210.20(A)

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

What size breaker do I need for a 24 amp load?

If the load is continuous, 24 × 1.25 = 30 A, which is itself a standard size, so a 30 A breaker. If it is non-continuous, 24 A rounds up to the next standard rating of 25 A. The same load number gives two different answers depending on how long it runs, which is why load type is the first thing to establish.

What counts as a continuous load?

The NEC defines it as a load whose maximum current is expected to continue for three hours or more. It is about duration at full current, not about how often the equipment is switched on. A lighting circuit in a shop that opens all day is continuous; a kitchen receptacle circuit, even a busy one, generally is not.

Why can I not use a 35 amp breaker on a 32 amp load?

You can, if the load is non-continuous — 35 A is a standard rating and it exceeds 32 A. The catch is the conductor: the breaker protects the wire, so a 35 A device needs a conductor with at least 35 A of ampacity after derating. Many people reach for the next breaker up without re-checking that the wire still qualifies.

Can I round up to the next breaker size if the load does not fit?

Rounding the device up to the next standard rating is normal and expected, since the calculated figure rarely lands on a listed size. What you cannot do is round up past what the conductor can carry. Where the conductor ampacity itself falls between standard ratings, 240.4(B) permits the next size up only for circuits rated 800 A or less and only where the conductor is not supplying receptacles.

Does the 125% rule apply to the neutral as well?

The neutral is sized to carry the maximum unbalanced current on the circuit, calculated under 220.61, rather than by applying the 125% factor directly. On a straightforward two-wire circuit the neutral carries the same current as the ungrounded conductor and ends up the same size in practice.

How do I convert watts to amps for this calculation?

For a single-phase load, divide watts by volts: 2880 W at 120 V is 24 A. For a balanced three-phase load, divide by the voltage times 1.732, so 10 kW at 480 V is about 12 A. Both assume a power factor of one, which holds for resistive loads such as heating and incandescent lighting but overstates the current for motors and electronics.