Ampacity Calculator

Work out the safe current-carrying capacity of a copper or aluminium conductor after ambient temperature and conductor bundling are taken into account — for electricians and designers sizing branch circuits and feeders to the NEC.

Last checked against the code

Ampacity Calculator

NEC (US)
Conductor material

How this is calculated

Ampacity is a thermal limit, not an electrical one. Current flowing through a conductor dissipates power as heat, and the published ampacity is the current at which the conductor settles at its insulation temperature rating and stops getting hotter. Exceed it and the insulation degrades long before the copper itself is in any danger.

Every figure in NEC Table 310.16 is quoted at two specific reference conditions: an ambient of 30 °C, and no more than three current-carrying conductors sharing a raceway or cable. Both conditions concern how easily heat escapes. Raise the ambient and the conductor has less temperature difference to shed heat across; add conductors to the same pipe and each one is heating its neighbours. So the calculation is a lookup followed by two independent reductions:

  • Correction for ambient, from Table 310.15(B)(1). Below 30 °C the factor is greater than one and the conductor may carry more than its table value.
  • Adjustment for bundling, from Table 310.15(C)(1). Four to six conductors gives 0.80, seven to nine 0.70, and it falls to 0.35 above forty.

Where both conditions exist the two factors multiply rather than applying in sequence, and the result is rounded once at the end. Two further limits then sit on top of the answer without changing it: 110.14(C) caps the circuit at the ampacity column matching the lowest-rated termination, and 240.4(D) fixes the maximum overcurrent device for 14, 12 and 10 AWG whatever the arithmetic produced. Those two constrain the breaker, not the conductor's thermal capacity, which is why this calculator reports them separately rather than folding them into the headline figure.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

Take a 10 AWG copper THHN conductor pulled through EMT across an unconditioned attic. Four current-carrying conductors share the conduit — two circuits, no shared neutral — and the attic reaches 40 °C on a summer afternoon. The breakers and lugs at both ends are listed for 75 °C, which is typical.

Step one, the base value. THHN is a 90 °C insulation, so the starting point is the 90 °C copper column of Table 310.16. For 10 AWG that is40 A.

Step two, ambient correction. 40 °C falls in the 36–40 °C band of Table 310.15(B)(1). Reading down to the 90 °C column gives a factor of0.91. So 40 × 0.91 = 36.4 A.

Step three, bundling adjustment. Four current-carrying conductors falls in the 4–6 band of Table 310.15(C)(1), a factor of 0.80. So 36.4 × 0.80 = 29.12, which rounds to 29 A.

Now the two ceilings. The 75 °C value for 10 AWG copper is 35 A, so 110.14(C) is not binding here — 29 A is already below it. The 240.4(D) cap for 10 AWG copper is 30 A, also above our figure. In this case the derating is what governs, and the conductor is good for 29 A.

The largest standard device at or below 29 A is 25 A. Note how easily this could have been missed: the same conductor in a 30 °C room with three conductors would have been a straightforward 30 A circuit. The attic and the fourth conductor between them cost roughly a quarter of the capacity.

Visual comparison

Ampacity by conductor size — copper, 75 °C, no deratingFixed conditions: copper, 75 °C column, 30 °C ambient, three current-carrying conductors. Notice that ampacity climbs far more slowly than cross-section: 4/0 has about twenty times the area of 10 AWG but only about six and a half times the ampacity, because heat escapes from the surface while current flows through the whole section.
Ampacity by conductor size — copper, 75 °C, no derating
SizeBarAmpacity (A)
14 AWG20
12 AWG25
10 AWG35
8 AWG50
6 AWG65
4 AWG85
3 AWG100
2 AWG115
1 AWG130
1/0 AWG150
2/0 AWG175
3/0 AWG200
4/0 AWG230
250 kcmil255
300 kcmil285
350 kcmil310
400 kcmil335
500 kcmil380
600 kcmil420
700 kcmil460
750 kcmil475

Source: NEC 2023 Table 310.16

Reference tables

Below is the whole of the base table this calculator draws on: every size from 14 AWG to 750 kcmil, in copper and aluminium, across all three insulation columns. Read across from the conductor size, pick the column matching the insulation printed on the jacket, and that is the ampacity before any correction — at 30 °C with three or fewer current-carrying conductors.

Use the table directly when your installation actually is at those reference conditions, which covers a great deal of ordinary interior work: a two-wire branch circuit in a conditioned space needs no factors at all, and the table value is the final answer. Reach for the calculator above as soon as ambient, bundling, or both come into play, because the factors compound and the intermediate figure is easy to round in the wrong place. The dashes in the aluminium row for 14 AWG are not an omission — Table 310.16 does not list aluminium below 12 AWG.

NEC Table 310.16 — allowable ampacities, copper and aluminium
SizeCu 60 °CACu 75 °CACu 90 °CAAl 60 °CAAl 75 °CAAl 90 °CA
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055304045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
Source: NEC 2023 Table 310.16. Values apply at 30 °C ambient with no more than three current-carrying conductors.

Common mistakes

  1. Treating the 90 °C column as a usable rating

    THHN is a 90 °C conductor, but almost no breaker or lug is listed above 75 °C. The 90 °C column is a legitimate starting point for derating and nothing else — the finished circuit is still capped at the 75 °C (or 60 °C) value for that size.

    NEC 2023 110.14(C)

  2. Leaving ambient at 30 °C when the run is not

    An uninsulated attic in July reaches 50 °C or more, and a boiler room is worse. At 50 °C a 90 °C conductor keeps only 0.82 of its rating and a 75 °C conductor keeps 0.75, before any bundling loss is applied.

    NEC 2023 Table 310.15(B)(1)

  3. Counting the wrong conductors for bundling

    Equipment grounding conductors never count. A neutral counts only where it carries unbalanced current on a three-wire circuit or where harmonics on a wye system make it a current-carrying conductor. Miscounting by one can cross a band boundary.

    NEC 2023 310.15(E)

  4. Forgetting the small-conductor cap on 14, 12 and 10 AWG

    Even where derating leaves 12 AWG copper at 24 A, overcurrent protection stays at 20 A. The cap is independent of the ampacity table and independent of your derating arithmetic, barring the specific exceptions.

    NEC 2023 240.4(D)

  5. Applying only the worse of the two factors

    Correction and adjustment are separate requirements from separate tables and both apply when both conditions exist. They multiply — a 0.91 ambient factor with an 0.80 bundling factor leaves 0.728 of the base, not 0.80.

    NEC 2023 310.15

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

What is the ampacity of 12 AWG copper wire?

In the 75 °C column of Table 310.16 it is 25 A, and in the 90 °C column 30 A. In practice a 12 AWG copper branch circuit is protected at 20 A, because 240.4(D) caps overcurrent protection for that size regardless of the table value. The 25 A figure only becomes relevant when 12 AWG is used as part of a larger assembly where the exceptions in 240.4(E) through (G) apply.

Does the length of the run change the ampacity?

No. Ampacity is a thermal limit set by how fast a conductor sheds heat, and a longer conductor heats and cools in the same proportion along its whole length. Length drives voltage drop instead, which is a separate calculation and frequently the reason a long run needs a larger conductor than ampacity alone would call for.

When does the neutral count as a current-carrying conductor?

On a balanced three-phase four-wire wye circuit the neutral carries only the unbalance and is not counted. It does count on a three-wire circuit fed from a four-wire wye system, and on any circuit where the major portion of the load is nonlinear, because harmonic currents add in the neutral rather than cancelling. Getting this wrong shifts you between the 1–3 and 4–6 bands.

Can I load THHN to its 90 °C ampacity?

Only if every termination in the circuit is listed for 90 °C, which is rare on standard breakers and lugs. The usual pattern is to start from the 90 °C column, apply correction and adjustment, and then confirm the result does not exceed the 75 °C value for that conductor. Whichever is lower governs.

Do short conduit nipples need the bundling adjustment?

No. A nipple of 600 mm (24 in.) or less between enclosures is exempt from the conductor adjustment factors, on the basis that heat escapes into the boxes at either end. Ambient temperature correction still applies to a nipple, and the conduit fill limits are relaxed to 60 percent rather than removed.

Why is aluminium rated lower than copper at the same size?

Aluminium has roughly 61 percent of copper’s conductivity, so the same cross-section generates more heat for the same current and reaches its insulation limit sooner. The practical rule is to go up one to two sizes when substituting aluminium — 4/0 aluminium at 180 A in the 75 °C column is close to 2/0 copper at 175 A.