Wire Size Calculator

Work out the minimum conductor for a load and a run length, checked against both ampacity and voltage drop, with the tool telling you which of the two decided the answer — for electricians and designers specifying a circuit rather than checking one.

Last checked against the code

Wire Size Calculator

NEC (US)

Other standards: BS 7671 / AS 3000, in mm²

What do you know about the load?
Phase
Sets the multiplier in the drop formula: 2 for single phase, 1.732 for a balanced three-phase load.

Derived load current:

Conductor material
Load type
Continuous means three hours or more at maximum current. It multiplies the current by 1.25 before both checks run, so it can move the answer a whole size on its own.

How this is calculated

A conductor has to pass two separate tests, and this calculator runs both and hands you whichever answer is larger. The tests measure different things and neither implies the other, which is the whole reason a page like this exists.

Test one is ampacity. The conductor has to carry the current without its insulation cooking. That figure comes from NEC Table 310.16, read at the temperature column of the insulation you are installing. Distance does not enter into it at all — a 10 ft run and a 500 ft run of the same conductor have exactly the same ampacity. Two rules ride along with the table: 240.4(D) caps the overcurrent device on 14, 12 and 10 AWG regardless of what the column says, and 110.14(C) holds the circuit to its lowest-rated termination, which is why the 75 °C column is usually the honest one to work from.

Test two is voltage drop. The conductor also has to deliver usable voltage at the far end, and here distance is the entire problem. The calculation solves for cross-sectional area directly, in circular mils:

CM = (2 × K × I × D) ÷ Vdrop for single phase, with 1.732 in place of the 2 for a balanced three-phase load. D is the one-way distance in feet, Vdrop is your percentage target converted to volts. K comes from a single site-wide definition — 12.9 for copper, with aluminium 64% higher because it conducts that much worse — and thevoltage drop calculator carries the full note on where that figure comes from and how far it moves between references. What matters here is which way the error points: the value used runs slightly pessimistic, so a size chosen against it has margin rather than needing some.

Both tests are run at the design current rather than the raw nameplate figure: a continuous load — three hours or more at maximum — is multiplied by 1.25 first, and that inflated figure is carried into the drop calculation as well as the ampacity lookup. That is the conservative reading, and the result panel shows the drop at the real operating current alongside it so you can see the difference the choice makes.

The larger of the two answers wins, and the tool names which one it was. That label matters more than it looks: if drop won, a shorter route or a higher system voltage buys you a size back, and more copper is the expensive way to solve it.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

A 40 A continuous load — a piece of shop equipment running all day — at 240 V single phase, 150 ft from the panel, copper conductors with 75 °C insulation, and a 3% drop target. Both paths, end to end.

The design current. The load is continuous, so 40 × 1.25 =50 A. Everything below runs on that figure.

The ampacity path. Reading down the 75 °C copper column of Table 310.16: 10 AWG is 35 A, which is short. 8 AWG is 50 A — exactly the design current, and 8 AWG is past the 240.4(D) sizes so nothing caps it. The ampacity-constrained answer is 8 AWG, with zero margin.

The voltage-drop path. The budget is 3% of 240 V =7.2 V. So the area needed is (2 × 12.9 × 50 × 150) ÷ 7.2 = 193,500 ÷ 7.2 = 26,875 circular mils. Looking up the ladder: 6 AWG is 26,240 cmil — 635 short. 4 AWG is 41,740 cmil, which clears it. The drop-constrained answer is 4 AWG.

The answer. 4 AWG is two sizes larger than 8 AWG, so4 AWG is the recommendation and voltage drop is what drove it. At that size the actual drop is 193,500 ÷ 41,740 = 4.64 V, or1.93% — well inside target, and 1.55% at the real 40 A operating current.

The interesting number is the one that lost. 6 AWG comes to 193,500 ÷ 26,240 = 7.37 V, or 3.07%. It misses a 3% target by seven hundredths of a percentage point, and jumping to 4 AWG for that margin is a real cost across a long pull. This is exactly where the 3% figure being a recommendation rather than enforceable code becomes a design conversation rather than a compliance one — and exactly why the calculator reports what the next size down would have done.

Visual comparison

Where voltage drop overtakes ampacityBoth constraints across a 300 ft range at your load. The dashed line is flat because ampacity cannot see distance — it is the same conductor at 25 ft and at 300. The copper staircase is voltage drop, climbing a size at a time. Where it crosses the dashed line, the run rather than the load starts setting the conductor.
  • Minimum by voltage drop
  • Minimum by ampacity
Where voltage drop overtakes ampacity — data
One-way distance (ft)Minimum by voltage dropkcmilMinimum by ampacitykcmilWhich binds, and at what size
256.516.58 AWG — ampacity wins over 12 AWG
5010.416.58 AWG — ampacity wins over 10 AWG
7516.516.58 AWG either way
10026.216.56 AWG — drop wins over 8 AWG
12526.216.56 AWG — drop wins over 8 AWG
15041.716.54 AWG — drop wins over 8 AWG
17541.716.54 AWG — drop wins over 8 AWG
20041.716.54 AWG — drop wins over 8 AWG
22541.716.54 AWG — drop wins over 8 AWG
25052.616.53 AWG — drop wins over 8 AWG
27552.616.53 AWG — drop wins over 8 AWG
30066.416.52 AWG — drop wins over 8 AWG

Source: NEC 2023 Table 310.16 for ampacity; circular-mil method at K = 12.9 for drop

At 50 A on this 240 V circuit, voltage drop overtakes ampacity at about 100 ft. Shorter than that and the load sets the size; longer and the run does.

Reference tables

The calculator is worth running for any circuit you are actually going to install. This table is for the other situation — standing in front of a panel deciding whether a proposed run is going to be a problem at all, and wanting a feel for where the boundary sits rather than a specific answer.

Every row is 240 V single phase, copper, 75 °C insulation, against a 3% target, and the load column is taken as the design current already: multiply a continuous load by 1.25 before you look it up. Read the last column first. The pattern it shows is that the crossover distance falls as the load grows in the small sizes and then rises again — 20 A is already drop-bound at 100 ft, 40 A is still balanced there, and 100 A is back to being ampacity-bound. That is not a quirk of the numbers; it is the ampacity ladder stepping in coarser jumps than the circular-mil requirement does, so how much slack a size has depends on where on the ladder you land.

What the table cannot tell you is what to do about a row you do not like. A load that comes out drop-bound by two sizes is usually cheaper to fix by moving the supply than by upsizing the conductor — and at 480 V the same load in the same conductor drops a quarter as much.

Which constraint binds, at 240 V single phase, copper, 75 °C, 3% target
LoadAOne-way runftBy ampacityBy voltage dropRecommendedWhat bindsActual drop
205012 AWG14 AWG12 AWGAmpacity1.65%
2010012 AWG10 AWG10 AWGVoltage drop2.07%
2020012 AWG8 AWG8 AWGVoltage drop2.6%
401008 AWG8 AWG8 AWGBoth, equally2.6%
402008 AWG4 AWG4 AWGVoltage drop2.06%
601006 AWG6 AWG6 AWGBoth, equally2.46%
602006 AWG3 AWG3 AWGVoltage drop2.45%
1001003 AWG4 AWG3 AWGAmpacity2.04%
1003003 AWG2/0 AWG2/0 AWGVoltage drop2.42%
Source: NEC 2023 Table 310.16 and 240.4(D) for the ampacity column; circular-mil method at K = 12.9 for the drop column.

Notes and exceptions

This page and the voltage drop calculator are opposite directions through the same physics. The voltage drop calculator is diagnostic: you already have a conductor and a run, and you want to know what the drop comes to. This one is prescriptive: you have a load and a run, and you want to know what to pull. If you are checking an existing circuit or an as-built, that one is the right tool. If you are specifying a circuit that does not exist yet, this one is, because a drop figure on its own does not tell you which size to buy.

What this calculator deliberately does not do. It assumes the reference conditions of Table 310.16 — a 30 °C ambient and no more than three current-carrying conductors in a raceway — so a hot roof space or a shared conduit needs the ampacity side re-checked with correction and adjustment factors applied. It sizes one conductor rather than a paralleled set. It does not handle motor circuits, which are sized from the Article 430 full-load current tables rather than from nameplate amps. And it uses the circular-mil approximation throughout, which ignores conductor reactance — negligible on the small sizes and short runs most branch work involves, but worth stepping up to the Chapter 9 Table 9 method on large conductors in steel raceway.

Common mistakes

  1. Sizing for ampacity alone and ignoring voltage drop

    This is the most common wire-sizing error in the field. The table gives a legal answer and nobody re-checks the run length, so a 250 ft branch circuit gets the same conductor a 25 ft one would. Nothing trips; the equipment at the far end just underperforms for the next thirty years.

    NEC 2023 210.19(A) Informational Note 4

  2. Measuring the run in a straight line

    Distance means the length of conductor, not the distance between two points on a drawing. Vertical drops, the climb over a beam, the loop into and out of a junction box and the tail inside the panel all add up, and 20% over the plan measurement is normal.

  3. Sizing from the 90 °C column

    THHN is a 90 °C insulation, so the temptation is to use the 90 °C figure and gain a size. Terminations on breakers and lugs are almost always listed at 60 °C or 75 °C, and 110.14(C) holds the whole circuit to the lowest of them.

    NEC 2023 110.14(C)

  4. Forgetting that 240.4(D) outranks the table

    Twelve-gauge copper reads 25 A in the 75 °C column, which tempts people onto a 25 A circuit. The small-conductor rule caps its overcurrent device at 20 A whatever the table says, so the conductor is not usable at that current.

    NEC 2023 240.4(D)

  5. Treating a drop answer as final without checking derating

    Both checks here assume the reference conditions of Table 310.16: a 30 °C ambient, three or fewer current-carrying conductors. A run through a hot attic or a raceway shared with three other circuits derates the ampacity side and can move the answer again.

    NEC 2023 310.15

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

What size wire do I need for a 40 amp load 150 feet away?

At 240 V single phase in copper with 75 °C insulation, and treating the load as continuous, you need 4 AWG. Ampacity alone would allow 8 AWG, which carries 50 A comfortably. Voltage drop is what forces the larger conductor: over 150 feet, 8 AWG would lose close to 5% of the supply, and even 6 AWG lands at 3.07%, just past a 3% target.

Does voltage drop or ampacity decide the wire size?

Whichever demands more copper — they are separate checks and either can win. Short runs with heavy loads are decided by ampacity: the conductor has to carry the current, and the length is too short to lose much. Long runs with modest loads are decided by voltage drop. The crossover between the two moves with the load, the voltage and the material, which is why the calculator plots it rather than quoting a rule of thumb.

Is the 3% voltage drop limit actually required by the NEC?

In most cases, no. The 3% branch-circuit and 5% combined figures appear in informational notes to 210.19(A) and 215.2(A)(2), and informational notes are explanatory rather than enforceable. Several specific articles do mandate a figure — 690.8 for photovoltaic circuits and 647.4(D) for sensitive electronic equipment among them — and local amendments sometimes make 3% binding, so check the jurisdiction before treating it as optional.

Do I use the one-way distance or the total length of wire?

Enter the one-way distance, from the panel to the load. The formula accounts for the return path itself: the factor of 2 in the single-phase version is exactly that. Entering the round-trip length doubles the calculation and produces a conductor one or two sizes larger than the circuit needs.

How much bigger does aluminium have to be than copper?

Roughly two sizes, on both constraints. Aluminium has about 61% of the conductivity of copper for the same cross-section, which is why its K value is 21.2 against copper’s 12.9 and why its ampacity column runs lower. Two AWG steps is close to a 60% increase in area, which is why the substitution lands where it does — but check the terminations are rated AL or CU-AL before making it.

What happens if my wire is undersized for voltage drop but not ampacity?

Nothing that will trip a breaker, which is precisely why the fault survives inspection. Motors draw more current at reduced voltage and run hotter, heating elements deliver less heat than their nameplate, LED drivers flicker or drop out at the bottom of their input range, and contactor coils chatter. The losses also show up as heat in the conductor and on the bill.