AWG Wire Size Calculator

Look up the diameter, cross-sectional area and resistance of any AWG or kcmil conductor, or work backwards from a measurement to the nearest standard gauge — for anyone holding a wire, reading a spec sheet, or checking what is already installed.

Last checked against the code

AWG Wire Size Calculator

What are you starting from?
Material
Diameter and area are the same either way — only resistance changes.

How this is calculated

American Wire Gauge is not a measurement system so much as amanufacturing log. Wire is drawn by pulling a rod through a die that squeezes it slightly narrower, then through a smaller die, and again, and the gauge number is a count of those passes. More passes means a thinner wire, which is the whole reason the numbering appears to run backwards.

It was later formalised as a geometric series between two fixed points: 36 AWG is 0.005 inches in diameter, 4/0 is 0.46 inches, and there are 39 steps between them. So every step multiplies the diameter by the 39th root of 92, about 0.8905. Three consequences fall straight out of that ratio and are worth carrying around: six gauge steps halve the diameter, six steps quarter the area, and ten steps divide the area by roughly ten.

Area is quoted in circular mils, a unit invented to make this arithmetic painless. One circular mil is the area of a circle one mil across, which means the area in circular mils is just the diameter in mils squared — no pi anywhere. A 12 AWG conductor measures 80.8 mils, and 80.8 squared is 6,530 circular mils, precisely what the tables print.

The series stops at 4/0, since continuing would need negative gauge numbers. Beyond it, conductors are named directly by area in thousands of circular mils: 250 kcmil, 500 kcmil and so on. Resistance is then simply resistivity divided by area — about 10.371 ohm-circular-mils per foot for copper at 20 °C — which is why resistance falls as area rises, and why aluminium at roughly 17.0 comes out around 64% more resistive for the same gauge.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

The tool runs in two directions, and both are worth walking through.

Forward: you have a size and want its properties. Take12 AWG copper, the most common branch-circuit conductor in North American residential work. Its diameter is 0.0808 inches, which is 2.052 mm. Squaring the diameter in mils gives 80.8² = 6,530 circular mils, or 3.31 mm². Resistance follows from area: 10.371 divided by 6,530, times 1,000, comes to about 1.59 ohms per 1,000 feet at 20 °C. The NEC works at 75 °C instead, where the same conductor is listed at 1.98 ohms per 1,000 feet — roughly 25% higher, because copper gets more resistive as it warms.

Reverse: you have a wire and want to know what it is. Suppose you are working on an existing installation with no markings legible on the jacket. You strip a short length and a caliper across the bare conductor reads about0.064 inches. Scanning the table for the closest standard diameter gives 14 AWG at 0.0641 inches — a difference of one ten-thousandth of an inch, well inside the tolerance of a hand measurement. The next size up, 12 AWG at 0.0808 inches, is 26% away, so there is no ambiguity about which it is.

Two cautions on that second case. Measure the bare conductor, because a reading across the insulation will be several gauges out on small wire. And if the conductor is stranded, a caliper reads wider than the equivalent solid diameter quoted here, since the strands do not pack perfectly — so treat a stranded reading as an upper bound and check the area figure instead where you can.

Visual comparison

Diameter across the standard rangeRead left to right: 14 AWG, 12 AWG, 10 AWG and on to 750 kcmil. The gauge number falls while the line climbs, which is the whole confusion in one picture. Note how gently the line rises at the left — several gauge steps barely move the diameter — and how steeply it climbs once kcmil sizes begin.
Diameter across the standard range — data
SizeDiameterin
14 AWG0.0641
12 AWG0.0808
10 AWG0.1019
8 AWG0.1285
6 AWG0.162
4 AWG0.2043
3 AWG0.2294
2 AWG0.2576
1 AWG0.2893
1/0 AWG0.3249
2/0 AWG0.3648
3/0 AWG0.4096
4/0 AWG0.46
250 kcmil0.5
300 kcmil0.5477
350 kcmil0.5916
400 kcmil0.6325
500 kcmil0.7071
600 kcmil0.7746
700 kcmil0.8367
750 kcmil0.866

Source: AWG geometric series; kcmil figures are equivalent solid diameters.

Reference tables

Both tables below cover the full standard range, 14 AWG through 750 kcmil. They are split by what you are looking for rather than crammed into one very wide table: dimensions first, then resistance for both materials at both reference temperatures.

Use the dimensions table when you are matching a physical wire or converting between AWG and metric. Use the resistance table for voltage-drop work, and pick the column that matches your basis — 20 °C for a bench calculation or a manufacturer's datasheet, 75 °C for anything following NEC practice. The calculator above does the same lookups and additionally works backwards from a measurement, which the tables cannot.

Unlike the other calculators on this site, nothing here depends on a code edition. These are physical constants of the wire itself and do not change when a new NEC is published.

AWG and kcmil dimensions
SizeDiameterinDiametermmAreacircular milsAreamm²
14 AWG0.06411.6284,1102.08
12 AWG0.08082.0526,5303.31
10 AWG0.10192.58810,3805.261
8 AWG0.12853.26416,5108.367
6 AWG0.1624.11526,24013.3
4 AWG0.20435.18941,74021.15
3 AWG0.22945.82752,62026.67
2 AWG0.25766.54366,36033.62
1 AWG0.28937.34883,69042.41
1/0 AWG0.32498.252105,60053.49
2/0 AWG0.36489.266133,10067.43
3/0 AWG0.409610.4167,80085.01
4/0 AWG0.4611.68211,600107.2
250 kcmil0.512.7250,000127
300 kcmil0.547713.91300,000152
350 kcmil0.591615.03350,000177
400 kcmil0.632516.07400,000203
500 kcmil0.707117.96500,000253
600 kcmil0.774619.67600,000304
700 kcmil0.836721.25700,000355
750 kcmil0.86622750,000380
Source: AWG geometric series. kcmil diameters are equivalent solid figures derived from area.
DC resistance, ohms per 1000 ft
SizeCopper 20 °CΩ/kftCopper 75 °CΩ/kftAluminium 20 °CΩ/kftAluminium 75 °CΩ/kft
14 AWG2.5233.144.1375.17
12 AWG1.5881.982.6043.25
10 AWG0.99911.241.6382.04
8 AWG0.62820.7781.031.28
6 AWG0.39520.4910.64790.808
4 AWG0.24850.3080.40730.508
3 AWG0.19710.2450.32310.403
2 AWG0.15630.1940.25620.319
1 AWG0.12390.1540.20320.253
1/0 AWG0.098210.1220.1610.201
2/0 AWG0.077920.09670.12770.159
3/0 AWG0.061810.07660.10130.126
4/0 AWG0.049010.06080.080350.1
250 kcmil0.041480.05150.068010.0847
300 kcmil0.034570.04290.056670.0707
350 kcmil0.029630.03670.048580.0605
400 kcmil0.025930.03210.042510.0529
500 kcmil0.020740.02580.0340.0424
600 kcmil0.017290.02140.028340.0353
700 kcmil0.014820.01840.024290.0303
750 kcmil0.013830.01710.022670.0282
Source: 20 °C derived from resistivity; 75 °C from NEC 2023 Chapter 9, Table 8 (uncoated).

Common mistakes

  1. Reading the gauge number as a size

    A bigger AWG number means a thinner wire. 10 AWG is thicker than 12 AWG, and 2 AWG is thicker still. The number counts drawing operations, not dimensions — it was originally how many times the wire was pulled through a die.

  2. Measuring over the insulation

    AWG describes the bare conductor. A caliper across the jacket reads several times too high on small sizes and will land you two or three gauges out. Strip a short length, or measure a cut end where the copper is exposed.

  3. Comparing a stranded conductor to a solid diameter

    A stranded conductor is wider than a solid one of the same cross-sectional area, because of the air between strands. All kcmil sizes are stranded, so a caliper reading across them will always exceed the equivalent solid figure quoted here.

  4. Assuming AWG and mm² sizes correspond

    They are separate systems with no clean conversion. 12 AWG is 3.31 mm², which sits between the metric 2.5 mm² and 4 mm² standard sizes. Substituting a metric cable for an AWG one always means rounding, and rounding down is the wrong direction.

  5. Using a resistance figure at the wrong temperature

    Copper resistance rises about 0.4% per degree Celsius. The 20 °C value is what wire tables quote; the NEC works at 75 °C, roughly 25% higher. Mixing the two into a voltage-drop calculation quietly understates the drop.

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

Is 10 gauge wire bigger than 12 gauge?

Yes. 10 AWG is 0.1019 inches across against 0.0808 for 12 AWG, so it is about a quarter thicker and has roughly 59% more copper by area. The smaller number is always the larger wire. In practice that difference is what separates a 20 A branch circuit in 12 AWG from a 30 A one in 10 AWG, and it is also why 10 AWG is noticeably stiffer to bend into a device box.

What is the difference between AWG and kcmil?

They are two ways of naming the same thing, used at different scales. AWG is a geometric series that runs out at 4/0, the largest gauge it defines. Above that, conductors are named directly by area in thousands of circular mils, so 250 kcmil simply means 250,000 circular mils. The step from 4/0 to 250 kcmil is a change of naming convention, not a jump in the underlying series.

Why does the gauge number get smaller as the wire gets thicker?

Because the number records a manufacturing process rather than a measurement. Wire is made by pulling a rod through a die that reduces its diameter, then through a smaller one, and so on. The gauge is the count of those passes. A 20 AWG wire has been drawn many more times than a 4 AWG wire, so it ends up far thinner. Once 4/0 is reached the count would go negative, which is why the series stops and kcmil takes over.

How many circular mils are in a wire?

A circular mil is the area of a circle one mil (a thousandth of an inch) in diameter, and the unit exists so that the area in circular mils is simply the diameter in mils squared — no pi required. A 12 AWG conductor is 80.8 mils across, and 80.8² is about 6,530 circular mils, which is exactly the figure the tables list.

What size is 12 AWG in mm²?

3.31 mm². Note that this is not a standard metric cable size: IEC systems use 2.5 mm² and 4 mm², so 12 AWG falls between the two. Anyone substituting metric cable for an AWG specification has to go up to 4 mm² rather than down to 2.5 mm², since the smaller metric size has roughly 25% less copper than the AWG conductor it would replace.

Does wire gauge depend on whether it is copper or aluminium?

No. AWG describes physical dimensions, so a 6 AWG aluminium conductor is exactly the same diameter and cross-sectional area as a 6 AWG copper one. What differs is electrical performance: aluminium has roughly 61% of copper’s conductivity, so the same gauge has about 64% more resistance and correspondingly less current-carrying capacity.