Watts to Amps Calculator

Turn a wattage nameplate into the current a conductor actually has to carry — including the power factor step that a plain watts-divided-by-volts sum leaves out.

Last checked against the code

Watts to Amps Calculator

Updates as you type
V
Line-to-line for a three-phase supply, line-to-neutral for single.
Phase
Single phase divides by V alone; three phase divides by V × 1.732.
A ratio between 0 and 1, not a percentage. Use the nameplate figure where the equipment states one — these presets are typical values, not measurements.
CurrentSingle phase
—A

At 125% for a continuous loadWhere the breaker calculation starts, not its answer
—

I = W ÷ (V × PF) single phase · I = W ÷ (V × 1.732 × PF) three phase

How this is calculated

A wattage nameplate states real power: the energy the equipment converts into heat, light or motion every second. Current is a different quantity, and the two are only interchangeable when the load is a pure resistance. That gap is what this page is about, and it is why a converter that asks only for watts and volts is right about a toaster and wrong about a compressor.

In an alternating-current circuit, voltage and current are both sine waves. In a heating element they rise and fall together, so every ampere flowing is doing work and real power equals the voltage times the current. Put an inductive load on the same circuit — a motor winding, a transformer, a fluorescent ballast — and the current wave lags behind the voltage wave. Some of the current is now shuttling energy into the magnetic field and back out again twice per cycle without ever doing anything useful. The conductor still carries it. The breaker still sees it. The wattmeter does not.

Power factor is the ratio between the two: the real power divided by the product of voltage and current. It runs from 0 to 1, and it appears in the denominator here because a lower power factor means more current for the same watts:

Single phase: I = W ÷ (V × PF)
Three phase: I = W ÷ (V × 1.732 × PF)

The 1.732 on three phase is the square root of three. It is there because the three line-to-line voltages are 120 degrees apart in time, so the total power arrives more evenly and each conductor carries less current than a single-phase supply delivering the same watts would need. Use the line-to-line voltage with it — 208, 480 — not the line-to-neutral figure.

One thing the formula cannot tell you is which voltage to enter. That comes from the equipment, not from the building: a dryer plugged into a 240 V outlet is a 240 V load even in a house whose lighting circuits are 120 V.

Worked example

One full calculation with real numbers, so you can follow along and check the tool by hand.

Two loads with almost the same headline wattage, on two different circuits, ending up in two different places. Running them side by side is the fastest way to see what the power factor field is actually doing.

Case 1 — a 1,500 W space heater on a 120 V circuit. A heating element is a coil of resistance wire and nothing else, so the power factor is 1 and the sum is as simple as it looks: 1,500 ÷ (120 × 1) = 12.5 A. That figure is worth remembering, because 12.5 A is also the practical ceiling for a plug-in 120 V appliance. A 15 A circuit may carry 12 A continuously under the 125% rule, so a heater run all afternoon is already past what its circuit is meant to hold indefinitely — which is why 1,500 W appears on so many nameplates and 1,800 W on so few.

Case 2 — a 3,000 W motor on a 240 V circuit. Twice the wattage, twice the voltage. If the motor were a resistor the two would cancel and it would draw the same 12.5 A. It is not, and it does not. At a power factor of 0.85 the sum is 3,000 ÷ (240 × 0.85) = 14.71 A.

Put the two results together. Doubling the wattage bought nothing, because doubling the voltage cancelled it out exactly — and then the power factor added18% on top, entirely from current that does no work. Had you sized this circuit from the naive 12.5 A, you would be 2.2 A light before applying any code factor at all, and the error grows with every point the power factor drops: the same motor at 0.8 draws 15.63 A, and at 0.7 it draws 17.86 A.

Neither figure is a wire size yet. Case 2 is a motor, and motor circuits are sized from the Article 430 full-load current tables rather than from a nameplate wattage — the conversion tells you what to expect, and the tables tell you what to install.

Visual comparison

Current drawn by common wattages, at 120 V and 240 VBoth traces climb in a straight line, and the 240 V trace is exactly half the 120 V one at every point — doubling the supply voltage always halves the current for the same power. That constant ratio is why a 5,000 W dryer on 240 V draws less current than a 3,000 W heater on 120 V, and why the voltage field is not a detail you can skip.
  • At 120 V
  • At 240 V
Current drawn by common wattages, at 120 V and 240 V — data
PowerAt 120 VAAt 240 VA
500 W4.172.08
1,000 W8.334.17
1,500 W12.56.25
2,000 W16.678.33
3,000 W2512.5

Source: Unity power factor throughout, so the comparison isolates the voltage.

Reference tables

The table below is for recognising a figure rather than deriving one. Most of the time you are not converting a wattage you have never seen — you are checking whether the number on a nameplate is plausible, or working out roughly what is already on a circuit before adding to it.

Read the character column first. Every resistive row is exact: the current shown is the wattage divided by the voltage with no adjustment, and if you measured it with a clamp meter you would get that number. Every motor and electronic row has had a typical power factor applied, and those rows are estimates. A specific unit can sit well either side of them.

Note the voltage column. Four of these appliances are 240 V loads, and they sit in the same list on purpose: the dryer draws 5,000 W and less current than the 1,875 W hair dryer beside it. Anyone converting from a memorised "amps at 120 V" habit gets those four badly wrong.

What the table is not is a load calculation. Article 220 sets its own required figures and demand factors for dwelling loads, and a service sized by adding up typical wattages will be both non-compliant and, usually, far too large.

Typical appliance wattages and the current they draw
ApplianceTypical powerWNominal supplyVLoad characterPower factorCurrentA
Space heater (high setting)1,500120Resistive1.0012.5
Hair dryer1,875120Resistive1.0015.6
Toaster oven1,400120Resistive1.0011.7
Coffee maker900120Resistive1.007.5
Microwave oven1,200120Electronic0.9011.1
Window air conditioner (10,000 BTU)1,100120Motor0.9010.2
Refrigerator (running)200120Motor0.852
Dishwasher (with heated dry)1,200120Resistive0.9810.2
Vacuum cleaner1,000120Motor0.909.3
Desktop computer and monitor300120Electronic0.952.6
Garage door opener550120Motor0.805.7
Electric clothes dryer5,000240Resistive1.0020.8
Electric range (one large element)2,400240Resistive1.0010
Electric water heater4,500240Resistive1.0018.8
Level 2 EV charger (32 A)7,680240Electronic1.0032
Source: Typical nameplate values for equipment sold in the US, not a code table. Power factors are conventional figures for each class of load.

Common mistakes

  1. Assuming unity power factor on a motor load

    This is the one that costs money. A 3,000 W motor at 240 V is 12.5 A on a naive sum and 14.7 A in reality at 0.85 power factor — an 18% error, all of it in the direction that undersizes the conductor and the overload protection.

  2. Reading a VA or kVA rating as if it were watts

    Transformers, generators and UPS units are rated in apparent power, which already contains the reactive part. Entering a kVA figure here and then applying a power factor divides by it twice and inflates the current by roughly a quarter.

  3. Using a microwave’s cooking wattage

    The number on the front of the appliance is heating output, not input. A unit advertised as 1,000 W typically draws around 1,500 W from the receptacle. Every appliance has a real electrical nameplate, usually on the back or inside the door.

  4. Converting a 240 V appliance at 120 V

    A dryer, range or water heater is a 240 V load. Running its wattage against 120 V doubles the current and sends you looking for wire two sizes larger than the job needs. Check the nameplate voltage before the nameplate watts.

  5. Treating the answer as a breaker size

    This is the load current. A device that runs three hours or more is a continuous load, and both the breaker and the conductor are sized at 125% of it before anything is rounded to a standard rating.

    NEC 2023 210.20(A)

This tool provides planning estimates. Always verify final values against your local code and a licensed electrician.

Frequently asked questions

How many amps is 1,500 watts?

At 120 volts, 12.5 amps. At 240 volts, 6.25 amps. The voltage matters as much as the wattage, which is why a 1,500 W space heater fills most of a 15 A kitchen circuit while a 1,500 W element in a 240 V water heater barely troubles its own. Both figures assume a resistive load; a 1,500 W motor at 0.85 power factor would be 14.7 A at 120 V.

What power factor should I use if the nameplate does not give one?

For anything with a heating element — heaters, ovens, incandescent lamps, electric water heaters — use 1.0, because a resistor genuinely has no reactive component. For a motor running at or near full load, 0.85 is a defensible working figure, and 0.8 is safer for something lightly loaded or old. For a modern switched-mode supply with power factor correction, 0.95. Where the equipment is a motor and the decision is a conductor size, take the current from the NEC full-load tables instead of deriving it at all.

How do I convert watts to amps on a three-phase supply?

Divide by the line-to-line voltage times 1.732, then by the power factor. A 10 kW three-phase load at 480 V is 10,000 ÷ (480 × 1.732) = 12.0 A at unity. The 1.732 is the square root of three, and it is there because the three phases peak at different moments, so the same power moves with less current in each conductor than a single-phase supply would need.

Is converting watts the same as converting VA?

No, and the difference is exactly the power factor. Watts is real power, the part doing work. VA is apparent power, the product of the voltage and the current that is actually flowing. On a resistive load they are the same number and the two conversions agree. On a motor they diverge, and the current is set by the VA figure rather than the watts. If your nameplate is in kVA, the kVA to amps converter is the tool that applies no power factor at all.

Does this work for DC circuits?

Yes, with the power factor left at 1 and the phase set to single. Direct current has no reactive component and no phase relationship, so watts divided by volts is the whole story. A 100 W load on a 12 V battery system draws 8.33 A. That is also why DC circuits at low voltage need surprisingly large conductors: the same power at 12 V draws ten times the current it would at 120 V.

Can I pick a breaker straight from this number?

Not directly. The converted figure is the load current, and a breaker is sized from it rather than set to it. If the load runs for three hours or more it is continuous, so the device and the conductor are both sized at 125% of this figure, and the result is then rounded up to a standard rating that manufacturers actually make. A 12.5 A continuous load becomes 15.63 A of required capacity and lands on a 20 A device.